Louvres can serve several purposes within a building, from providing airflow and protecting openings from wind-driven rain to screening plant and equipment or reducing noise transmission.
Each application brings different requirements, so selecting the right system starts with understanding what it needs to achieve.
Specifying the correct louvre starts with getting these five details right:
Define the application: Establish what the louvre needs to do and where it will be installed.
Determine the appropriate performance: Understand the ratings and select the level of protection the application needs.
Balance different requirements:
1. airflow
2. weather protection
3. screening
4. acoustics
Coordinate the design: Bring appearance, access, supporting structure and security into the specification.
Review the details early: Check for errors, omissions and conflicting requirements to reduce the risk of changes later.
Involving a louvre specialist such as Maple early can help establish that balance and identify potential specification issues before they affect delivery.
Before selecting a louvre, establish its purpose and location within the building. For example, a louvre protecting a ventilation opening may need to provide airflow while limiting rain ingress.
For rooftop screening, blade arrangement and viewing angles are important to effectively conceal equipment. An angled profile, such as the 140° blade used in Contour® SL, can help achieve the required screening whilst still allowing ventilation.
Where mechanical plant generates noise, such as at data centres, acoustic performance is often a high priority. At Frankfurt Data Centre, Maple’s Contour® acoustic louvres help reduce noise breakout from plant areas while maintaining a clean, consistent architectural appearance. These requirements should inform system selection from the outset, alongside the building services design and architectural intent.
Weather louvres are tested to BS EN 13030 for rain rejection and aerodynamic performance.
Rain rejection is classified from Class A to Class D, with Class A providing the highest level of protection at 99–100% effectiveness under the test conditions. However, performance varies with airflow velocity, so the classification should always be considered alongside the project’s design airflow requirements. A Class A rating does not mean a louvre is completely watertight under all conditions.
Aerodynamic performance is classified separately from Class 1 to Class 4, with Class 1 offering the lowest resistance to airflow. Features that improve rain defence can also increase airflow resistance, so both aspects need to be reviewed together.
Where louvres protect sensitive equipment or ventilation openings from wind-driven rain, a high level of rain defence may be essential. Class A weather protection, available with systems such as Contour® HP, may be appropriate here, provided the tested performance meets the project’s design airflow conditions.
For a louvre used primarily to screen rooftop plant, the same level of weather protection may not be required. Specifying a higher level of weather protection than needed could increase costs and restrict the choice of suitable systems without addressing the project’s main priority.
The aim is to select the performance needed for the application, supported by relevant test data.
Considering different requirements helps avoid selecting a system that meets one requirement at the expense of another.
Airflow requirements should be established and reviewed against the proposed louvre’s performance data. For example, Contour® VL is designed to achieve airflow performance coefficients of up to 0.315, helping balance ventilation and screening. Reviewing the relevant configuration against the required airflow and pressure drop helps determine its suitability.
Where noise control is needed, acoustic requirements introduce another consideration. Deeper profiles and acoustic infill can reduce sound transmission but also increase airflow resistance.
Acoustic test data should be reviewed against the project’s requirements, with input from an acoustic consultant where appropriate. Take a look at this article on Maple’s Knowledge Centre to learn more about how acoustic louvres are tested.
For buildings with heightened security requirements, additional measures such as security mesh may be needed behind the louvres. These should be reviewed alongside ventilation requirements, as mesh or guarding can introduce resistance to airflow.
As you can see, specifying the correct louvre for your project can be quite a balancing act, however Maple’s team can help you review suitable louvre systems and access the technical information needed to inform your decisions.
We also check specifications for errors, omissions and conflicting requirements. Identifying these issues early helps reduce the risk of unsuitable product selection, costly changes and delays further down the line.
Get in touch with Maple’s expert team for support with your louvre specification.